PowerShield Centurion 6000VA Tower overview
The Centurion Tower is PowerShield's true online double-conversion tower UPS for critical equipment. The PSCE6000 is rated 6000 VA / 6000 W (output power factor 1.0) and outputs a pure sine wave with zero transfer time from AC mode to battery mode. PowerShield designed it for critical power applications, remote locations more than 30 km from the city grid, light to heavy industrial environments, sites with generators and applications that need remote connectivity.
Outlets: 2 x 10 A IEC C13 outlets plus hard-wired terminal input and output. It runs on 20 internal 12 V 9 Ah batteries with a typical recharge of 7 hours to 90% capacity. Input and output are hard-wired terminals, so plan for a fixed electrical installation, and N+X parallel redundancy is available on the 6 kVA model.
Built for unstable power
A wide input voltage window (110–300 VAC at 50% load; 176–300 VAC at 100% load), input power factor correction of 0.99 or better, generator compatibility and a 50/60 Hz frequency converter mode suit regional and industrial sites. ECO mode reaches 98% efficiency when mains quality allows.
Management
USB and RS-232 are standard with HID support for Windows, Apple, Linux and NAS devices and the free PowerShield NetGuard software. The intelligent slot takes the PSSNMPV4 SNMP card, the PSAS400 relay card or a Modbus card, and programmable outlets plus EPO are built in.
Extending runtime
Backup time on the Centurion Tower is extended by plugging in additional battery banks. PowerShield's datasheet lists PSCEBB40 and the PSCEBB60CH (with its own 4 A charger) for 6 and 10 kVA models; see the runtime table below. These battery banks are available on request from ARC IP Networks. The Centurion Tower range runs from 1000 VA to 10000 VA.
PowerShield PSCE6000 specifications
At a glance
Warranty: 2 Years (3 Years with Registration)
| Model |
|---|
| PowerShield part number | PSCE6000 |
|---|
| Capacity | 6000 VA / 6000 W |
|---|
| Topology | True online double-conversion |
|---|
| Input |
|---|
| Nominal voltage | 208 / 220 / 230 / 240 VAC |
|---|
| Voltage range | 110–300 VAC at 50% load; 176–300 VAC at 100% load |
|---|
| Frequency range | 46–54 Hz or 56–64 Hz |
|---|
| Output |
|---|
| Output voltage | 240 VAC (selectable) |
|---|
| Transfer time, inverter to bypass | Zero |
|---|
| Outlets | 10 A C13 x 2; hard-wired terminal input/output |
|---|
| Battery |
|---|
| Internal batteries | 20 x 12 V 9 Ah |
|---|
| Typical recharge time | 7 hours to 90% capacity |
|---|
| Charging current (max.) | 4 A |
|---|
| Protection |
|---|
| Surge protection | 1,080 J / 30,000 A |
|---|
| Physical |
|---|
| Dimensions (D x W x H) | 592 x 250 x 576 mm |
|---|
| Environment |
|---|
| Noise level | < 55 dB at 1 m |
|---|
| Input |
|---|
| Input power factor correction | ≥ 0.99 at 100% load |
|---|
| Output |
|---|
| Frequency (battery mode) | 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz |
|---|
| Voltage regulation | ±1% |
|---|
| Current crest ratio | 3:1 |
|---|
| Transfer time, AC mode to battery mode | Zero |
|---|
| Waveform (battery mode) | Pure sine wave |
|---|
| Efficiency |
|---|
| ECO mode | 98% |
|---|
| Communications |
|---|
| Interface | USB and RS-232 as standard; intelligent slot for PSSNMPV4, PSAS400 dry contact or PSMBUS |
|---|
| Software | PowerShield NetGuard (Windows, Linux, Unix and Mac) |
|---|
| HID | Supports Windows, Apple, Linux, NAS and various industrial controllers |
|---|
| LCD display | UPS status, load level, battery level, input/output voltage, battery time remaining, fault indicators |
|---|
| Environment |
|---|
| Humidity / temperature | 20–95% RH non-condensing at 0–40 °C |
|---|
| Compliance |
|---|
| Safety / EMC | EN62040-1-1 2003, IEC60950-1-1, EN62040-2 2006 |
|---|
| Model |
|---|
| Parallel redundancy | N+X parallel redundancy available (6K/10K models) |
|---|
| PowerShield product listing |
|---|
| Form factor | Tower |
|---|
| Total outlets | 2 |
|---|
| Battery expandable | Yes |
|---|
| Phase | Single Phase |
|---|
| Net weight | 81 kg |
|---|
| Warranty |
|---|
| PowerShield Australian warranty | 2 years, extended free to 3 years when you register the UPS with PowerShield, with on-site service for this hardwired 6 kVA unit |
|---|
Source: PowerShield official specifications (PowerShield Centurion Tower UPS Product Brochure, PowerShield Centurion 6-10K Tower UPS User Manual (PF 1.0), Parallel Kit Installation). Runtime and efficiency figures are PowerShield published values; Specifications are subject to change by the manufacturer.
Download the PowerShield Centurion Tower UPS Product Brochure (PDF)
Centurion Tower 6000VA runtime at each load (PowerShield chart)
Load in VA at 0.7 power factor; minutes under optimal conditions; real runtime varies with temperature and battery age.
PSCE6000 battery runtime in minutes by load, from the PowerShield runtime chart| Load (VA) | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 | 5000 | 6000 | 7000 |
|---|
| Load (W at 0.7 PF) | 1400 | 1750 | 2100 | 2450 | 2800 | 3150 | 3500 | 4200 | 4900 |
|---|
| PSCE6000 alone | 46 | 35 | 28 | 24 | 21 | 18 | 16 | 13 | 10 |
|---|
| PSCE6000 + 1 x PSCEBB40 (available on request) | 172 | 132 | 108 | 90 | 80 | 70 | 61 | 49 | 40 |
|---|
| PSCE6000 + 1 x PSCEBB60CH (available on request) | 237 | 190 | 153 | 129 | 111 | 96 | 85 | 70 | 57 |
|---|
| PSCE6000 + 2 x PSCEBB40 (available on request) | 303 | 240 | 204 | 171 | 146 | 126 | 111 | 88 | 76 |
|---|
| PSCE6000 + 1 x PSCEBB40 (available on request) + 1 x PSCEBB60CH (available on request) | 367 | 295 | 245 | 213 | 184 | 158 | 139 | 111 | 91 |
|---|
| PSCE6000 + 2 x PSCEBB60CH (available on request) | 431 | 348 | 292 | 250 | 220 | 193 | 169 | 134 | 111 |
|---|
Source: PowerShield runtime comparison chart. Read how to read the PowerShield runtime chart.
Other PowerShield published runtime figures
PowerShield publishes these backup times for the PSCE6000 on its own and with Centurion Tower battery banks added. To size a UPS, PowerShield suggests adding the watts of the equipment to protect and dividing by 0.7 to get the VA rating the UPS must exceed.
| Configuration | 100% load (6000 VA) | 50% load (3000 VA) |
|---|
| PSCE6000 alone | 10 min | 28 min |
|---|
| + PSCEBB40 | 55 min | 110 min |
|---|
| + PSCEBB40 + PSCEBB60CH | 116 min | 232 min |
|---|
| + PSCEBB40 + PSCEBB60CH + PSCEBB40 | 170 min | 340 min |
|---|
Source: Centurion Tower brochure (each column adds the battery bank shown to the configuration on its left). Actual runtime varies with load, battery age and temperature.
Compatibility and fit
PowerShield accessories that match this model, from PowerShield's datasheets, battery selection guide and accessory listings (replacement batteries matched on the 12 V 9 Ah battery type):
- Replacement batteries: PSB12-9 (12V 9Ah Replacement UPS Battery), PSB12-9-10YR (12V 9Ah Long Life UPS Battery)
- Network and monitoring: PSSNMPV4 (SNMP V4 Network Management Card with EMD Port), PSEMD (Environmental Monitoring Device for SNMP V4), PSAS400D (AS400 Relay Comms Card), PSAS400T (AS400 Relay Comms Card), PSECB (External Comms Box for Two Comms Cards)
- Maintenance bypass and distribution: PSMBSW10K (10kVA Wall Mount Maintenance Bypass Switch for 6–10kVA UPS)
Other options listed in the PowerShield datasheet (ask ARC IP Networks to quote): PSModbus Modbus card; PSCEBB40 and PSCEBB60CH battery banks.